Motor starter, TeSys island, 80A at AC-1, 66A at AC-3, 37kW, 40hp, DOL type | TPRST080
New in

Motor starter, TeSys island, 80A at AC-1, 66A at AC-3, 37kW, 40hp, DOL type | TPRST080

  • TeSys island direct starter, 3 poles, 80A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 80A and motors up to 37kW@400V / 40hp@480V.
908,87 zł
net / szt.
Lowest price in 30 days before discount: / szt.
Regular price: / szt.
14 days for easy returns
This product is not available in a stationary store
Safe shopping
Deferred Payments. Buy now, pay later, if you don't return it
Buy now, pay later - 4 steps
When choosing a payment method, select PayPo.PayPo - buy now, pay later
PayPo will pay your bill in the store.
On the PayPo website, verify your information and enter your social security number.
After receiving your purchase, you decide what suits you and what doesn't. You can return part or all of your order - then the amount payable to PayPo will also be reduced.
Within 30 days of purchase, you pay PayPo for your purchases at no additional cost. If you wish, you spread your payment over installments.

TPRST080

TeSys island direct starter, 3 poles, 80A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 80A and motors up to 37kW@400V / 40hp@480V. It provides motor protection functions including thermal overload (setting 4-80A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Main

Range:

TeSys

Product name:

TeSys island

skrócona nazwa urządzenia:

TPRST

Motor starter type:

Direct on line

Function Available:

Upstream voltage presence detection
Electrical line and load protection
Power and energy monitoring when connected with TPRVM voltage module

Motor power kW:

18,5 kW at 230 V 50 Hz (AC-3)
37 kW at 380...415 V 50 Hz (AC-3)
37 kW at 440 V 50 Hz (AC-3)
37 kW at 500 V 50 Hz (AC-3)
37 kW at 690 V 50 Hz (AC-3)

motor power HP (UL / CSA):

5 hp at 120 V (AC) 60 Hz for 1 phase motors
10 hp at 240 V (AC) 60 Hz for 1 phase motors
20 hp at 208 V (AC) 60 Hz for 3 phase motors
20 hp at 240 V (AC) 60 Hz for 3 phase motors
40 hp at 480 V (AC) 60 Hz for 3 phase motors
50 hp at 600 V (AC) 60 Hz for 3 phase motors

Znamionowe napięcie łączeniowe [Ue]:

≤ 690 V (AC) 47...63 Hz

[Ie] rated operational current:

66 A (at <50 °C) at ≤ 440 V AC-3
80 A (at <50 °C) at ≤ 440 V AC-1

[Ith] conventional free air thermal current:

80 A (at 50 °C)

[Ui] rated insulation voltage:

690 V IEC 60947-4-1
600 V UL 60947-4-1
600 V CSA C22.2 No 60947-4-1

[Uimp] rated impulse withstand voltage:

6 kV zgodnie z IEC 61010-1

Thermal protection adjustment range:

4 ... 80 A

Thermal overload class:

Class 5 ... 30

RESET:

Remotely or automatically

Irms rated making capacity:

1000 A at 440 V conforming to IEC 60947

Rated breaking capacity:

1000 A at 440 V conforming to IEC 60947

[Icw] rated short-time withstand current:

900 A 40 °C - 1 s
520 A 40 °C - 10 s
260 A 40 °C - 1 min
110 A 40 °C - 10 min.

Average impedance:

1,5 mOm - Ith 80 A 50 Hz

Power dissipation per pole:

6,5 W AC-3
9,6 W AC-1

[Uc] control circuit voltage:

24 V DC supplied by the bus coupler

Current consumption:

80 mA contactor sealed
500 mA contactor closing

Power dissipation in W:

21,4 W at Ie AC-3

Complementary:

Mechanical durability:

6 Mcycles

Electrical durability:

0.75 Mcycles 66 A AC-3 440 V
0.5 Mcycles 80 A AC-1 440 V

Maximum operating rate:

3600 c./min AC-3

Operating time:

< 80 ms closing
< 80 ms opening

Dimensions

Width:

55 mm

Height:

167 mm

Depth:

125 mm

Environment

Stopień ochrony:

IP20

Ambient air temperature for operation:

-10 °C ... 50 °C without derating
-10 °C ... 60 °C with current derating

Ambient air temperature for storage:

od -25 °C do 70 °C

Korzyści

  • The TPRST TeSys island module protects the motor from overload, overheating, and failures
  • It allows monitoring of power, energy, currents, and voltages in cooperation with the TPRVM module.
  • It supports remote control and automatic reset through integration with the TPRBC bus.
  • Compliance with international standards and certifications ensures universal applicability.
pixel
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.
Ask a question
If this description is not sufficient, please send us a question to this product. We will reply as soon as possible. Data is processed in accordance with the privacy policy. By submitting data, you accept privacy policy provisions.
This page uses cookie files to provide its services in accordance to Cookies Usage Policy. You can determine conditions of storing or access to cookie files in your web browser.
Close