Motor starter, TeSys island, 40A at AC-1, 38A at AC-3, 18.5kW, 20hp, DOL type | TPRST038
- TeSys island direct starter, 3 poles, 38A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 38A and motors up to 18,5kW@400V / 20hp@480V.
TPRST065
TeSys island direct starter, 3 poles, 65A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 65A and motors up to 30kW@400V / 40hp@480V. It provides motor protection functions including thermal overload (setting 3.35-65A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Main |
---|
Range: |
|
Product name: |
|
Device short name: |
|
Product or Component Type: |
|
Motor starter type: |
|
Function Available: |
Upstream voltage presence detection |
Electrical line and load protection |
Power and energy monitoring when connected with TPRVM voltage module |
|
Motor power kW: |
9 kW at 230 V 50 Hz (AC-3) |
18.5 kW at 380...415 V 50 Hz (AC-3) |
18.5 kW at 440 V 50 Hz (AC-3) |
18.5 kW at 500 V 50 Hz (AC-3) |
18.5 kW at 690 V 50 Hz (AC-3) |
|
motor power HP (UL / CSA): |
2 hp at 120 V AC 60 Hz for 1 phase motors |
5 hp at 240 V AC 60 Hz for 1 phase motors |
10 hp at 208 V AC 60 Hz for 3 phase motors |
10 hp at 240 V AC 60 Hz for 3 phase motors |
20 hp at 480 V AC 60 Hz for 3 phase motors |
25 hp at 600 V AC 60 Hz for 3 phase motors |
|
[Ue] rated operational voltage: |
≤ 480 V AC 47...63 Hz for overvoltage cat. III |
≤ 690 V AC 47...63 Hz for overvoltage cat. II |
|
[Ie] rated operational current: |
38 A (at <50 °C) at ≤ 440 V AC-3 |
40 A (at <50 °C) at ≤ 440 V AC-1 |
|
[Ith] conventional free air thermal current: |
|
[Ui] rated insulation voltage: |
690 V IEC 60947-4-1 |
600 V UL 60947-4-1 |
600 V CSA C22.2 No 60947-4-1 |
|
[Uimp] rated impulse withstand voltage: |
|
Thermal protection adjustment range: |
|
Thermal overload class: |
|
RESET: |
Remotely or automatically |
|
Irms rated making capacity: |
550 A at 440 V conforming to IEC 60947 |
|
Rated breaking capacity: |
550 A at 440 V conforming to IEC 60947 |
|
[Icw] rated short-time withstand current: |
430 A 40 °C - 1 s |
310 A 40 °C - 10 s |
150 A 40 °C - 1 min |
60 A 40 °C - 10 min. |
|
Average impedance: |
|
Power dissipation per pole: |
2.9 W AC-3 - Ith 38 A |
3.2 W AC-1 - Ith 40 A |
|
[Uc] control circuit voltage: |
24 V DC supplied by the bus coupler |
|
Current consumption: |
160 mA contactor sealed |
160 mA contactor closing |
|
Power dissipation in W: |
|
Complementary: |
---|
trwałość mechaniczna : |
|
Electrical durability: |
1.4 Mcycles 38 A AC-3 440 V |
2 Mcycles 40 A AC-1 440 V |
|
Maximum operating rate: |
|
Operating time: |
< 100 ms closing |
< 30 ms opening |
|
Dimensions |
---|
Width: |
|
Height: |
|
Depth: |
|
Environment |
---|
IP degree of protection: |
|
Ambient air temperature for operation: |
-10 °C ... 50 °C without derating |
50 °C ... 60 °C with current derating |
|
Ambient air temperature for storage: |
|
Korzyści
- Protects against overloads, overheating, phase loss, and other motor malfunction issues.
- Provides power and energy measurement, as well as monitoring of electrical parameters with the TPRVM module.
- Can be mounted vertically or horizontally on a DIN rail and is compatible with a wide range of wires.
- High mechanical durability (30 million cycles) and electrical durability (1.4 million cycles at 38 A AC-3).
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.