QUINT4-PS/3AC/24DC/40/IOL - Power supply | 1151047
- QUINT POWER primary circuit clocked power supplies, Screw connection, Mounting on mounting rail, Input: 3-phase, Output: 24 V DC / 40 A
Power supplies
Our power supplies are reliable and ideally suited for any application. In our diverse product portfolio, you will find DIN-rail power supplies that vary in design, power and features. This makes them an excellent choice for a wide range of industries, such as automotive, mechanical engineering, process industries, and for the shipbuilding industry. Product |
---|
Product type: | |
Product family: | |
AC mode |
---|
Input voltage range: | The range is from 3x 400 V AC to 500 V AC | Tolerance -20 % ... +10 % | The range is from 2x 400 V AC to 500 V AC | Tolerance -10% ... +10 % | |
Frequency range : | 50 Hz to 60 Hz | Tolerance ±10 Hz | |
Power backup time: | type. 26 ms (3x 400 V AC) | type. 26 ms (3x 480 V AC) | |
Current consumption: | type. 3x 1.8 A (400 V AC) | type. 3x 1.5 A (480 V AC) | type. 2x 3 A (400 V AC) | type. 2x 2.5 A (480 V AC) | type. 3x 1.5 A (500 V AC) | type. 2x 2.4 A (500 V AC) | |
Rated power consumption : | |
Protection system : | Protection against transient currents; Varistor, spark gap
gassed | |
DC mode |
---|
Input voltage range: | The range is from ± 260 V DC to 300 V DC | Tolerance -13% ... +30 % | |
Current consumption : | 2.2 A (±260 V DC) | 1.9 A (±300 V DC) | |
Rated power consumption : | |
Output data | Efficiency: | type. 95.4 % (400 V AC) | type. 95.4 % (480 V AC) | |
output power: | |
Start-up time: | < 1 s (UOut (10 % ... 90 %)) | |
High reliability: MTBF | > 849,000 hours at 25 °C | > 517,000 hours at 40 °C | > 236,000 hours at 60 °C | |
Parallel connectivity: | Yes, for redundancy and increased power | |
Serial connectivity: | |
Assembly | Mounting method | Mounting on a mounting rail | |
Mounting position | DIN rail horizontal NS 35, EN 60715 | |
Dimensions | Width: 120 mm | Height: 130 mm | Depth: 125 mm | |
Ambient conditions | Degree of protection | |
Ambient temperature | from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) | |
Standard designation: Standards/Regulations | Railroad applications | EN 50121-3-2 | EN 50121-5 | IEC 62236-3-2 | IEC 62236-5 | |
HART FSK Physical Layer Test Specification Compliance | Output voltage UOut compatible | |
Normative limitation of higher harmonics of the network current | |
Normative low protection voltage | IEC 61010-1 (SELV) | IEC 61010-2-201 (PELV) | |
Normative certain separation | |
Standard - Safety requirements for equipment
measuring, control, regulation and laboratory equipment | |
Normative safety of transformers | |
Charging the battery | |
Approval - semiconductor industry requirements for
with respect to supply voltage drops. | SEMI F47-0706, EN 61000-4-11 | |
Benefits
- Enables easy system expansion, reliable triggering of large loads and tripping of overcurrent circuit breakers.
- High fault tolerance thanks to a gassed spark gap (up to 6 kV) and a power backup time of ≥ 20 ms in the event of a grid failure.
- Preventive monitoring function reports critical operating states before failure occurs.
- Possibility to integrate with all industrial networks thanks to built-in IO-Link interface and direct connection to QUINT-UPS or CAPAROC circuit breaker system.
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.