QUINT4-PS/3AC/24DC/5 - Power supply | 2904620
- QUINT POWER primary circuit clocked power supply, selectable output characteristics, SFB (Selective Fuse Breaking) technology and NFC connector, input: 3-phase, output: 24 V DC / 5 A
Power supplies
Power supplies
Our power supplies are reliable and ideally suited for any application. In our diverse product portfolio, you will find DIN-rail power supplies that vary in design, power and features. This makes them an excellent choice for a wide range of industries, such as automotive, mechanical engineering, process industries, and for the shipbuilding industry.
Product |
Product type: |
|
Product family: |
|
AC mode |
Input voltage range: |
The range is from 3x 400 V AC to 500 V AC |
Tolerance -20 % ... +10 % |
The range is from 2x 400 V AC to 500 V AC |
Tolerance -10% ... +10 % |
|
Frequency range: |
50 Hz to 60 Hz |
Tolerance ±10 Hz |
|
Power backup time: |
type. 34 ms (3x 400 V AC) |
type. 50 ms (3x 480 V AC) |
|
Current consumption: |
type. 3x 0.53 A (400 V AC) |
type. 3x 0.44 A (480 V AC) |
type. 2x 0.9 A (400 V AC) |
type. 2x 0.66 A (480 V AC) |
type. 3x 0.45 A (500 V AC) |
type. 2x 0.8 A (500 V AC) |
|
Rated power consumption : |
|
Protection system : |
Protection against transient currents; Varistor, spark gap
gassed |
|
DC mode |
Input voltage range: |
The range is from ± 260 V DC to 300 V DC |
Tolerance -25% ... +30 % |
|
Current consumption : |
|
Output data |
Efficiency: |
type. 89 % (400 V AC) |
type. 87.5 % (480 V AC) |
|
Short circuit resistance and idle test: |
|
output power: |
|
Start-up time: |
< 50 ms (UOut (10 % ... 90 %)) |
|
High reliability: MTBF |
> 1,560,000 hours at 25 °C |
> 914,000 hours at 40 °C |
> 413,000 hours at 40 °C |
|
Parallel connectivity: |
Yes, for redundancy and increased power |
|
Serial connectivity: |
|
Assembly |
Mounting method |
Mounting on a mounting rail |
|
Mounting position |
DIN rail horizontal NS 35, EN 60715 |
|
Dimensions |
 |
Width: 36 mm |
Height: 130 mm |
Depth: 125 mm |
|
Ambient conditions |
Degree of protection |
|
Ambient temperature |
from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations |
Railroad applications |
EN 50121-3-2 |
EN 50121-4 |
EN 50121-5 |
IEC 62236-3-2 |
IEC 62236-4 |
IEC 62236-5 |
|
Normative limitation of higher harmonics of the network current |
|
Normative electrical safety |
|
normative low protection voltage |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Normative certain separation |
IEC 61558-2-16 |
IEC 61010-2-201 |
|
Standard - Safety requirements for equipment
measuring, control, regulation and laboratory equipment |
|
Normative safety of transformers |
|
Standardized power devices for low voltage and
dC outputs |
|
Benefits
- Provides selective tripping of standard overcurrent circuit breakers, allowing connected loads to operate simultaneously.
- Function reports critical operating states before failure occurs.
- Adjustable signaling thresholds and characteristics maximize system availability.
- Thanks to static power reserve and starting devices with higher consumption with dynamic power reserve.
- Integrated gasified spark gap and power backup time of more than 20 ms.
- Metal housing and temperature range from -40°C to +70°C.
- Can be used in any country thanks to wide-range input and international certification.
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.