QUINT4-PS/1AC/24DC/40 - Power supply | 2904603
- QUINT POWER primary circuit clocked power supply, selectable output characteristics, SFB (Selective Fuse Breaking) technology and NFC connector, input: 1-phase, output: 24 V DC / 40 A
Power Supplies
Our power supplies are reliable and perfectly suited for any application. In our diverse product portfolio you will find DIN rail power supplies that vary in design, power, and features. This makes them an excellent choice for many industries, such as the automotive industry, machinery construction, processing, and the maritime sector.
Product |
Product Type: |
|
Product Family: |
|
AC Mode |
Input Voltage Range: |
The range is from 100 V AC to 240 V AC |
Tolerance -15% ... +10% |
|
Input Frequency Range fN: |
from 50 Hz to 60 Hz |
Tolerance ±10 Hz |
|
Power Hold-up Time: |
typ. 29 ms (120 V AC) |
typ. 32 ms (230 V AC) |
|
Current Consumption: |
typ. 13.6 A (100 V AC) |
typ. 10 A (120 V AC) |
typ. 5.2 A (230 V AC) |
typ. 5.4 A (240 V AC) |
|
DC Mode |
Input Voltage Range: |
The range is from 110 V DC to 250 V DC |
Tolerance -18% ... +40% |
|
Current Consumption: |
12 A (110 V DC) |
5 A (250 V DC) |
|
Output Data |
Efficiency: |
typ. 94.8% (120 V AC) |
typ. 95.9% (230 V AC) |
|
Short-circuit Resistance and No-load Test: |
|
Output Power: |
|
High Reliability: MTBF |
> 934,000 hours at 25 °C |
> 555,000 hours at 40 °C |
> 249,000 hours at 60 °C |
|
Parallel Connection Capability: |
Yes, for redundancy and increased power |
|
Series Connection Capability: |
|
Output Data |
Efficiency: |
typ. 94.8% (120 V AC) |
typ. 95.9% (230 V AC) |
|
Short-circuit Resistance and No-load Test: |
|
Output Power: |
|
High Reliability: MTBF |
> 934,000 hours at 25 °C |
> 555,000 hours at 40 °C |
> 249,000 hours at 60 °C |
|
Mounting |
Mounting Method: |
Mounting on a mounting rail |
|
Mounting Position: |
On a horizontal support rail NS 35/7.5 and NS 35/15 according to EN 60715 |
|
Dimensions: |
Width: 40 mm |
Height: 130 mm |
Depth: 132 mm, 125 mm (Device depth (mounting on a DIN rail)) |
|
Ambient Conditions |
Protection Rating: |
|
Ambient Temperature: |
from -25 °C to 70 °C (> 60°C nominal parameter reduction: 2.5% per K) |
|
Standard Designation: Standards/Regulations |
Overvoltage Category: |
EN 61010-1 II (≤ 4000 m) |
EN 61010-2-201 II (≤ 4000 m) |
|
Extra Low Voltage PELV: |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Benefits
- The module provides easy network integration thanks to the PROFINET, EtherNet/IP, EtherCAT® and USB connectors.
- It monitors the battery's state of health (SOH) and state of charge (SOC).
- It automatically detects the battery's capacity and technology, such as VRLA-WTR and lithium-ion.
- It enables monitoring of the output current and voltage as well as manual system on/off control.
- It selectively triggers standard overcurrent protection devices, allowing devices connected in parallel to continue operating without interruptions.
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.