QUINT4-PS/3AC/24DC/20 - Power supply | 2904622
- QUINT POWER primary circuit clocked power supply, selectable output characteristics, SFB (Selective Fuse Breaking) technology and NFC connector, input: 3-phase, output: 24 V DC / 20 A
Power Supplies
Our power supplies are reliable and perfectly suited for any application. In our diverse product portfolio, you will find DIN rail-mounted power supplies available in various designs, power ratings, and functions. As a result, they are an excellent choice for a wide range of industries, such as automotive, mechanical engineering, process industry, and shipbuilding.
Product |
Product Type: |
|
Product Family: |
|
AC Mode |
Input Voltage Range: |
Range from 3x 400 V AC to 500 V AC |
Tolerance -20% ... +10% |
Range from 2x 400 V AC to 500 V AC |
Tolerance -10% ... +10% |
|
Frequency Range: |
50 Hz to 60 Hz |
Tolerance ±10 Hz |
|
Power Hold-up Time: |
typical 33 ms (3x 400 V AC) |
typical 33 ms (3x 480 V AC) |
|
Current Draw: |
typical 3x 0.99 A (400 V AC) |
typical 3x 0.81 A (480 V AC) |
typical 2x 1.62 A (400 V AC) |
typical 2x 1.37 A (480 V AC) |
typical 3x 0.8 A (500 V AC) |
typical 2x 1.23 A (500 V AC) |
|
Rated Power: |
|
Protection System: |
Protection against transient currents; varistor, gas discharge tube |
|
DC Mode |
Input Voltage Range: |
Range from ±260 V DC to 300 V DC |
Tolerance -13% ... +30% |
|
Current Draw: |
1.23 A (±260 V DC) |
1.06 A (±300 V DC) |
|
Output Specifications |
Efficiency: |
typical 93.9% (400 V AC) |
typical 93.8% (480 V AC) |
|
Short-circuit Resistance and No-load Test: |
|
Output Power: |
|
Start-up Time: |
< 80 ms (UOut (10% ... 90%)) |
|
High Reliability: MTBF |
> 985 000 hours at 25 °C |
> 638 000 hours at 40 °C |
> 311 000 hours at 60 °C |
|
Parallel Connectivity: |
Yes, for redundancy and increased power |
|
Series Connectivity: |
|
Mounting |
Mounting Method: |
Mounting on a mounting rail |
|
Mounting Position: |
Horizontal DIN rail NS 35, EN 60715 |
|
Dimensions: |
|
Width: 70 mm |
Height: 130 mm |
Depth: 125 mm |
|
Environmental Conditions |
Protection Rating: |
|
Ambient Temperature: |
from -25 °C to 70 °C (> 60 °C, reduction: 2.5% per K) |
|
Standard Marking: Standards/Regulations |
Rail Applications: |
EN 50121-3-2 |
EN 50121-4 |
EN 50121-5 |
IEC 62236-3-2 |
IEC 62236-4 |
IEC 62236-5 |
|
Limit on Higher Harmonics of Mains Current: |
|
Normative Electrical Safety: |
|
Normative Protective Low Voltage: |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Normative Isolation: |
IEC 61558-2-16 |
IEC 61010-2-201 |
|
Standard - Safety Requirements for Measuring, Controlling, Regulating, and Laboratory Equipment:
|
|
Normative Transformer Safety: |
|
Battery Charging: |
|
Approval - Semiconductor Industry Requirements for Power Supply Voltage Drops:
|
SEMI F47-0706, EN 61000-4-11 |
|
Benefits
- SFB technology enables selective tripping of standard overcurrent circuit breakers, allowing simultaneous operation of connected loads.
- The function alerts critical operating conditions before a failure occurs.
- Adjustable signaling thresholds and characteristics maximize system availability.
- Featuring a static power reserve and starters with higher power draw with dynamic power reserve.
- Integrated gas discharge tube and a power hold-up time of over 20 ms.
- Metal enclosure and an operating temperature range from -40°C to +70°C.
- It can be used in any country thanks to a wide input voltage range and international certification.