QUINT4-PS/3AC/24DC/40 - Power supply | 2904623
- QUINT POWER primary circuit clocked power supply, selectable output characteristics, SFB (Selective Fuse Breaking) technology and NFC connector, input: 3-phase, output: 24 V DC / 40 A
Power supplies
Our power supplies are reliable and ideally suited for any application. In our diverse product portfolio, you will find DIN-rail power supplies that vary in design, power and features. This makes them an excellent choice for a wide range of industries, such as automotive, mechanical engineering, process industries, and for the shipbuilding industry.
Product
|
Product type:
|
|
Product family:
|
|
AC mode
|
Input voltage range:
|
The range is from 3x 400 V AC to 500 V AC |
Tolerance -20 % ... +10 % |
The range is from 2x 400 V AC to 500 V AC |
Tolerance -10% ... +10 % |
|
Frequency range:
|
50 Hz to 60 Hz |
Tolerance ±10 Hz |
|
Power backup time:
|
type. 28 ms (3x 400 V AC) |
type. 28 ms (3x 480 V AC) |
|
Current consumption:
|
type. 3x 1.8 A (400 V AC) |
type. 3x 1.8 A (480 V AC) |
type. 2x 3 A (400 V AC) |
type. 2x 2.5 A (480 V AC) |
type. 3x 1.5 A (500 V AC) |
type. 2x 2.4 A (500 V AC) |
|
Rated power consumption :
|
|
Protection system :
|
Protection against transient currents; Varistor, spark gap
gassed |
|
DC mode
|
Input voltage range:
|
The range is from ± 260 V DC to 300 V DC |
Tolerance -13% ... +30 % |
|
Current consumption :
|
2.2 A (±260 V DC) |
1.9 A (±300 V DC) |
|
Rated power consumption :
|
|
Output data
|
Efficiency:
|
type. 95.7 % (400 V AC) |
type. 95.7 % (480 V AC) |
|
Short circuit resistance and idle test:
|
|
output power:
|
|
Start-up time:
|
< 1 s (UOut (10 % ... 90 %)) |
|
High reliability: MTBF
|
> 849,000 hours at 25 °C |
> 517,000 hours at 40 °C |
> 236,000 hours at 60 °C |
|
Parallel connectivity:
|
Yes, for redundancy and increased power |
|
Serial connectivity:
|
|
Assembly
|
Mounting method
|
Mounting on a mounting rail |
|
Mounting position
|
DIN rail horizontal NS 35, EN 60715 |
|
Dimensions
|
Width: 120 mm |
Height: 130 mm |
Depth: 125 mm |
|
Ambient conditions
|
Degree of protection
|
|
Ambient temperature
|
from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations
|
Railroad applications
|
EN 50121-3-2 |
EN 50121-5 |
IEC 62236-3-2 |
IEC 62236-5 |
|
Normative limitation of higher harmonics of the network current
|
|
Normative electrical safety
|
|
Normative low protection voltage
|
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Normative certain separation
|
IEC 61558-2-16 |
IEC 61010-2-201 |
|
Standard - Safety requirements for equipment
measuring, control, regulation and laboratory equipment
|
|
Normative safety of transformers
|
|
Charging the battery
|
|
Approval - semiconductor industry requirements for
with respect to supply voltage drops
|
SEMI F47-0706, EN 61000-4-11 |
|
Benefits
- Enables simple system expansion, reliable triggering of large loads and efficient tripping of overcurrent circuit breakers.
- Resistance to disturbances thanks to spark-gassing (up to 6 kV) and provision of power supply backup for at least 20 ms in case of network failure.
- Preventive function monitoring informs of critical operating conditions before failure occurs.
- The device can be ordered configured according to your needs, even in quantities of one unit.
Wszystkie parametry znajdują się poniżej w karcie produktu