QUINT4-PS/1AC/24DC/5 - Power supply | 2904600
- QUINT POWER power supply clocked in primary circuit, selectable output characteristics, SFB (Selective Fuse Breaking) technology and NFC connector, input: 1-phase, output: 24 V DC / 5 A
Power supplies
Our power supplies are reliable and ideally suited for any application. In our diverse product portfolio, you will find DIN-rail power supplies that vary in design, power and features. This makes them an excellent choice for a wide range of industries, such as automotive, mechanical engineering, process industries, and for the shipbuilding industry.
Product
|
Product type:
|
|
Product family:
|
|
AC mode
|
Input voltage range:
|
The range is from 100 V AC to 240 V AC |
Tolerance -15% ... +10 % |
|
Frequency range :
|
50 Hz to 60 Hz |
Tolerance ±10 Hz |
|
Power backup time:
|
type. 28 ms (120 V AC) |
type. 38 ms (230 V AC) |
|
Current consumption:
|
type. 1.7 A (100 V AC) |
type. 1.5 A (120 V AC) |
type. 0.9 A (230 V AC) |
type. 0.8 A (240 V AC) |
|
Rated power consumption :
|
|
Protection system :
|
Protection against transient currents; Varistor, spark gap
gassed |
|
DC mode
|
Input voltage range:
|
The range is from 110 V DC to 250 V DC |
Tolerance -18% ... +40 % |
|
Current consumption :
|
1.6 A (110 V DC) |
0.7 A (250 V DC) |
|
Output data
|
Efficiency:
|
type. 88.8 % (120 V AC) |
type. 89.2 % (230 V AC) |
|
Short circuit resistance and idle test:
|
|
output power:
|
|
Start-up time:
|
< 50 ms (UOut (10 % ... 90 %)) |
|
High reliability: MTBF
|
> 1,532,000 hours at 25 °C |
> 930,000 hours at 40 °C |
> 431,000 hours at 60 °C |
|
Parallel connectivity:
|
Yes, for redundancy and increased power |
|
Serial connectivity:
|
|
Assembly
|
Mounting method
|
Mounting on a mounting rail |
|
Mounting position
|
DIN rail horizontal NS 35, EN 60715 |
|
Dimensions
|
|
Width: 36 mm |
Height: 130 mm |
Depth: 125 mm |
|
Ambient conditions
|
Degree of protection
|
|
Ambient temperature
|
from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations
|
Railroad applications
|
EN 50121-3-2 |
EN 50121-4 |
EN 50121-5 |
EN 50163 |
IEC 62236-3-2 |
IEC 62236-4 |
IEC 62236-5 |
|
Normative limitation of higher harmonics of the network current
|
|
Normative electrical safety
|
|
Normative low protection voltage
|
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Normative certain separation
|
IEC 61558-2-16 |
IEC 61010-2-201 |
|
Standard - Safety requirements for equipment
measuring, control, regulation and laboratory equipment
|
|
Normative safety of transformers
|
|
Standardized power devices for low voltage and
dC outputs
|
|
Charging the battery
|
|
Approval - semiconductor industry requirements for
with respect to supply voltage drops.
|
SEMI F47-0706, EN 61000-4-11 |
|
Benefits
- Provides selective tripping of standard overcurrent circuit breakers, allowing connected loads to operate simultaneously.
- Function reports critical operating states before failure occurs.
- Adjustable signaling thresholds and characteristics maximize system availability.
- Thanks to static power reserve and starting devices with higher consumption with dynamic power reserve.
- Integrated gasified spark gap and power backup time of more than 20 ms.
- Metal housing and temperature range from -40°C to +70°C.
- Can be used in any country thanks to wide-range input and international certification.
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.