Product |
Product type: |
|
Product family: |
|
AC mode |
Input voltage range: |
| The range is from 100 V AC to 240 V AC |
| Tolerance -15% ... +10 % |
| The range is from 115 V AC to 240 V AC |
| Tolerance ±10 % (UL) |
|
Frequency range (fN): |
| 50 Hz to 60 Hz |
| Tolerance ±10 % |
|
Power backup time: |
| > 27 ms (120 V AC) |
| > 28 ms (230 V AC) |
|
Current consumption: |
| type. 2.6 A (100 V AC) |
| type. 2.2 A (120 V AC) |
| type. 1.2 A (230 V AC) |
| type. 1.1 A (240 V AC) |
|
Protection system: |
| Protection against transient currents; Varistor |
|
DC mode |
Input voltage range: |
| The range is from 100 V DC to 240 V DC |
| Tolerance ±10 % |
| The range is from 160 V DC to 240 V DC |
| Tolerance ±10 % (UL) |
|
Current consumption: |
| type. 2.7 A (100 V AC) |
| type. 1.1 A (240 V AC) |
|
Output data |
Efficiency: |
| type. 94.5 % (at 120 V AC) |
| type. 95.5 % (at 230 V AC) |
|
Reducing the rating parameters: |
| < 100 V AC (1 % for each V) |
| > 60°C (2.5% for each K) |
|
Output power: |
|
Start-up time: |
| ≤ 1 s (UOUT (10 % ... 90 %)) |
|
High reliability: MTBF |
| > 2,300,000 hours at 25 °C |
| > 1,300,000 hours at 40 °C |
| > 610,000 hours at 60 °C |
|
Parallel connectivity: |
| Yes, to increase power and redundancy |
|
Serial connectivity: |
| Yes, to increase voltage (observe SELV limit) |
|
Signaling |
Signaling methods |
| LED DC OK - signal status operation |
|
Function |
| Visual indication of working condition. |
|
Assembly |
Mounting method |
| Mounting on a mounting rail |
|
Mounting position |
| DIN rail horizontal NS 35, EN 60715 |
|
Dimensions |
| Width: 40 mm |
| Height: 135 mm |
| Depth: 132 mm, 125 mm (Depth of device (DIN rail mounting)) |
|
Ambient conditions |
Degree of protection |
|
Ambient temperature |
| from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations |
EN 61010-1 |
| III (≤ 2000 m) |
| II (≤ 5000 m) |
|
EN 61010-2-201 |
| III (≤ 2000 m) |
| II (≤ 5000 m) |
|
Safety in the use of power supplies up to 1100 V (clearances insulation) |
|
Electrical safety |
|
Equipping electrical power equipment with auxiliary electronic devices |
|
Safety requirements for measuring devices, control, regulation and laboratory |
|
Very low voltage PELV |
| IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) |
|
Safe insulation |
| IEC 61558-2-16 |
| IEC 61010-2-201 |
|
Permissible levels of harmonic current emissions |
|
Network fluctuation / undervoltage condition |
|