Product |
Product type: |
|
Product family: |
|
AC mode |
Input voltage range: |
The range is from 100 V AC to 240 V AC |
Tolerance -15% ... +10 % |
The range is from 115 V AC to 240 V AC |
Tolerance ±10 % (UL) |
|
Frequency range (fN): |
50 Hz to 60 Hz |
Tolerance ±10 % |
|
Power backup time: |
> 27 ms (120 V AC) |
> 28 ms (230 V AC) |
|
Current consumption: |
type. 2.6 A (100 V AC) |
type. 2.2 A (120 V AC) |
type. 1.2 A (230 V AC) |
type. 1.1 A (240 V AC) |
|
Protection system: |
Protection against transient currents; Varistor |
|
DC mode |
Input voltage range: |
The range is from 100 V DC to 240 V DC |
Tolerance ±10 % |
The range is from 160 V DC to 240 V DC |
Tolerance ±10 % (UL) |
|
Current consumption: |
type. 2.7 A (100 V AC) |
type. 1.1 A (240 V AC) |
|
Output data |
Efficiency: |
type. 94.5 % (at 120 V AC) |
type. 95.5 % (at 230 V AC) |
|
Reducing the rating parameters: |
< 100 V AC (1 % for each V) |
> 60°C (2.5% for each K) |
|
Output power: |
|
Start-up time: |
≤ 1 s (UOUT (10 % ... 90 %)) |
|
High reliability: MTBF |
> 2,300,000 hours at 25 °C |
> 1,300,000 hours at 40 °C |
> 610,000 hours at 60 °C |
|
Parallel connectivity: |
Yes, to increase power and redundancy |
|
Serial connectivity: |
Yes, to increase voltage (observe SELV limit) |
|
Signaling |
Signaling methods |
LED DC OK - signal status operation |
|
Function |
Visual indication of working condition. |
|
Assembly |
Mounting method |
Mounting on a mounting rail |
|
Mounting position |
DIN rail horizontal NS 35, EN 60715 |
|
Dimensions |
Width: 40 mm |
Height: 135 mm |
Depth: 132 mm, 125 mm (Depth of device (DIN rail mounting)) |
|
Ambient conditions |
Degree of protection |
|
Ambient temperature |
from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations |
EN 61010-1 |
III (≤ 2000 m) |
II (≤ 5000 m) |
|
EN 61010-2-201 |
III (≤ 2000 m) |
II (≤ 5000 m) |
|
Safety in the use of power supplies up to 1100 V (clearances insulation) |
|
Electrical safety |
|
Equipping electrical power equipment with auxiliary electronic devices |
|
Safety requirements for measuring devices, control, regulation and laboratory |
|
Very low voltage PELV |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Safe insulation |
IEC 61558-2-16 |
IEC 61010-2-201 |
|
Permissible levels of harmonic current emissions |
|
Network fluctuation / undervoltage condition |
|