- Primary circuit clocked power supplies, TRIO POWER, Push-in terminals, Mounting on mounting rail, Input: 3-phase, output: 24 V DC / 40 A, adjustable in 24 V DC range ... 28 V DC
Power supplies
Our power supplies are reliable and ideally suited for any application. In our diverse product portfolio, you will find DIN-rail power supplies that vary in design, power and features. This makes them an excellent choice for a wide range of industries, such as automotive, mechanical engineering, process industries, and for the shipbuilding industry. Product |
---|
Product type: | |
Product family: | |
AC mode |
---|
Input voltage range: | The range is from 3x 400 V AC to 500 V AC | Tolerance -20 % ... +10 % | The range is from 3x 400 V AC to 500 V AC | Tolerance ±10 % | |
Frequency range (fN): | 50 Hz to 60 Hz | Tolerance ±10 % | |
Power backup time: | type. 21 ms (3x 400 V AC) | type. 21 ms (3x 480 V AC) | |
Current consumption: | type. 3x 1.5 A (3x 400 V AC) | type. 3x 1.2 A (3x 500 V AC) | type. 3x 2.6 A (3x 400 V AC) | type. 3x 2.1 A (3x 500 V AC) | |
Protection system : | Protection against transient currents; Varistor | |
Output data | Efficiency: | type. 95.4 % (at 3x 400 V AC) | type. 98.8 % (at 3x 480 V AC) | |
Reducing the rating parameters: | |
output power: | |
Start-up time: | ≤ 1 s (UOUT (10 % ... 90 %)) | |
High reliability: MTBF | > 1,200,000 hours at 25 °C | > 660,000 hours at 40 °C | > 265,000 hours at 60 °C | |
Parallel connectivity: | Yes, to increase power and redundancy with diode | |
Serial connectivity: | Yes, to increase voltage (observe SELV limit) | |
Syngalization | Signaling methods | LED DC OK - signal status operation | |
Function | Visual indication of working condition. | |
Assembly | Mounting method | Mounting on a mounting rail | |
Mounting position | DIN rail horizontal NS 35, EN 60715 | |
Dimensions | Width: 90 mm | Height: 135 mm | Depth: 167 mm, 160 mm (Depth of device (DIN rail mounting)) | |
Ambient conditions | Degree of protection | |
Ambient temperature | from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) | |
Standard designation: Standards/Regulations | EN 61010-1 | III (≤ 2000 m) | II (≤ 5000 m) | |
EN 61010-2-201 | III (≤ 2000 m) | II (≤ 5000 m) | |
Safety in the use of power supplies up to 1100 V (clearances
insulation) | |
Electrical safety | |
Equipping electrical power equipment with auxiliary electronic devices | |
Safety requirements for measuring devices,
control, regulation and laboratory | |
Very low voltage PELV | IEC 61010-1 (SELV) | IEC 61010-2-201 (PELV) | |
Safe insulation | IEC 61558-2-16 | IEC 61010-2-201 | |
Permissible levels of harmonic current emissions | |
Network fluctuation / undervoltage condition | |
Benefits
- Compact size and in-line option saves space.
- Dynamic power reserve with robust output characteristics for durability and reliability.
- Push-in connection technology for simple and quick installation.
- Multi-color LEDs and collective contact provide clear status indication, optional with IO-Link.
- Integrated multi-channel switch combines power and protection in a single device, increasing system availability.

Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.