- QUINT capacitive module, with maintenance-free energy storage based on double-layer capacitors, Mounting on mounting rail, input: 24 V DC, output: 24 V DC / 20 A / 16 kJ with mounted universal DIN rail adapter UTA 107
UPS modules
DC UPS module guarantees maximum system reliability, providing uninterrupted power supply even in the event of network failure. With this solution, you will avoid downtime and potential losses that can result from sudden power outages. Continuing key processes becomes possible and your operations remain secure and efficient. Choose the right UPS solution with energy storage or built-in capacity to enjoy peace of mind and confidence that your system will operate reliably in any situation. Product |
---|
Product type: | |
Product family: | |
Input Data |
---|
Input voltage range: | The range is from 22.5 V DC to 30 V DC | |
Current consumption: | IN = 20 A | IMax = 30 A | INo-Load = 0,1 A | ICharge = 10 A | PN = 488 W | PMax = 599 W | ICharge = 244 W | |
Output data | Efficiency: | > 98 % (with charged energy storage) | |
Short circuit resistance and idle test: | |
Output power: | |
Output current: | |
High reliability: MTBF | > 1,351,036 hours at 25 °C | > 903,325 hours at 40 °C | > 470,143 hours at 60 °C | |
Parallel connection possible : | |
Serial connectivity: | |
Assembly | Mounting method | Mounting on a mounting rail | |
Mounting position | DIN rail horizontal NS 35, EN 60715 | |
Dimensions | | Width: 244 mm | Height: 130 mm | Depth: 125 mm | |
Ambient conditions | Degree of protection | |
Ambient temperature | from -25 °C to 60 °C (> 40 °C derating: 1 % for each K) | |
Standard designation: Standards/Regulations | Surge category | EN 61010-1 II (≤ 4000 m) | EN 61010-2-201 II (≤ 4000 m) | UL 60950-1 II (≤ 4000 m) | |
Very low voltage PELV | IEC 61010-1 (SELV) | IEC 61010-2-201 (PELV) | |
Benefits
- The module has an efficiency of more than 98%, which minimizes energy losses and reduces operating costs.
- Fast charging time of only 6 minutes ensures quick recovery to full operational readiness.
- Offers a wide input voltage range from 22.5 V DC to 30 V DC, with reverse polarity protection.
- It features an EtherNet/IP interface and supports Modbus/TCP protocols, allowing easy integration with control and monitoring systems.
- It has advanced short-circuit protection and test functions, meeting safety and electromagnetic compatibility standards.
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.