Product
|
Product type: |
|
Product family: |
|
AC mode
|
Input voltage range: |
The range is from 100V AC to 240V AC |
Tolerance -15% ... +10 % |
|
Frequency range : |
50 Hz to 60 Hz |
Tolerance ± 10% |
|
Power backup time: |
> 25 ms (120 V AC) |
> 25 ms (230 V AC) |
|
Current consumption: |
type. 1.34 A (100 V AC) |
type. 1.1 A (120 V AC) |
type. 0.59 A (230 V AC) |
type. 0.57 A (240 V AC) |
|
Protection system: |
Transient overvoltage protection; Varistor |
|
Input fuse: |
3.15 A internal (equipment protection), delayed |
|
Output data
|
Efficiency: |
type. 93 % (120 V AC) |
type. 94 % (230 V AC) |
|
Rated output voltage: |
|
Rated output current (IN): |
|
Short circuit resistance and idle test: |
|
Reducing the rating parameters: |
< 100 V AC (1 % for each V) |
|
output power: |
|
Start-up time: |
< 1 s (UOut = 10 % ... 90 %) |
|
High MTBF reliability: |
> 1,442,000 hours at 25 °C |
> 813,000 hours at 40 °C |
> 428,000 hours at 55 °C |
|
Parallel connection possible: |
yes, to increase power and redundancy with diode |
|
Serial connectivity: |
yes, to increase the voltage |
|
Syngalization
|
Signaling methods |
LED DC OK - operation signal status (UN = 24 V DC, IOut = IN) |
|
Function |
Visual indication of working condition. |
|
Assembly
|
Mounting method |
Mounting on a mounting rail |
|
Mounting position |
DIN rail horizontal NS 35, EN 60715 |
|
Dimensions |
Width: 35 mm |
Height: 130 mm |
Depth: 129 mm, 125 mm (Depth of device (DIN rail mounting)) |
|
Ambient conditions
|
Degree of protection |
|
Ambient temperature |
from -25 °C to 70 °C (> 55 °C reduction: 2.5 % for each K) |
|
Standard designation: Standards/Regulations
|
Surge category |
EN 61010-1 |
II (≤ 4000 m) |
|
EN 62477-1 |
III (≤ 3000 m) |
|
Safety of use of power supplies up to 1100 V (insulation gaps) |
|
Electrical safety |
|
Normative electrical safety |
|
Equipping power equipment with auxiliary electronic devices |
|
Safety requirements for measuring, control, regulation and laboratory equipment |
|
Very low voltage PELV |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Safe insulation |
IEC 61558-2-16 |
IEC 61010-2-201 |
|
Permissible levels of harmonic current emissions |
|
The requirements of the semiconductor industry in with regard to voltage drops in the supply |
SEMI F47 - 0706 (180 V AC) |
|