Product |
Product type: |
|
Product family: |
|
AC mode |
Input voltage range: |
| The range is from 3x 400 V AC to 500 V AC |
| Tolerance -20 % ... +10 % |
| The range is from 2x 400 V AC to 500 V AC |
| Tolerance ±10 % |
|
Frequency range (fN): |
| 50 Hz to 60 Hz |
| Tolerance ±10 % |
|
Power backup time: |
| type. 35 ms (3x 400 V AC) |
| type. 58 ms (3x 480 V AC) |
|
Current consumption: |
| type. 3x 0.68 A (3x 400 V AC) |
| type. 3x 0.57 A (3x 500 V AC) |
| type. 2x 1.3 A (2x 400 V AC) |
| type. 2x 1.1 A (2x 500 V AC) |
|
Protection system: |
| Protection against transient currents; Varistor |
|
Output data |
Efficiency: |
| type. 92.3 % (at 3x 400 V AC) |
| type. 92.4 % (at 3x 480 V AC) |
|
Reducing the rating parameters: |
|
Output power: |
|
Start-up time: |
| ≤ 1 s (UOUT (10 % ... 90 %)) |
|
High reliability: MTBF |
| > 1,400,000 hours at 25 °C |
| > 820,000 hours at 40 °C |
| > 320,000 hours at 60 °C |
|
Parallel connectivity: |
| Yes, to increase power and redundancy |
|
Serial connectivity: |
| Yes, to increase voltage (observe SELV limit) |
|
Syngalization |
Signaling methods |
| LED DC OK - signal status operation |
|
Function |
| Visual indication of working condition. |
|
Assembly |
Mounting method |
| Mounting on a mounting rail |
|
Mounting position |
| DIN rail horizontal NS 35, EN 60715 |
|
Dimensions |
| Width: 40 mm |
| Height: 135 mm |
| Depth: 132 mm, 125 mm (Depth of device (DIN rail mounting)) |
|
Ambient conditions |
Degree of protection |
|
Ambient temperature |
| from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations |
EN 61010-1 |
| III (≤ 2000 m) |
| II (≤ 5000 m) |
|
EN 61010-2-201 |
| III (≤ 2000 m) |
| II (≤ 5000 m) |
|
Safety in the use of power supplies up to 1100 V (clearances insulation) |
|
Electrical safety |
|
Equipping electrical power equipment with auxiliary electronic devices |
|
Safety requirements for measuring devices, control, regulation and laboratory |
|
Very low voltage PELV |
| IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) |
|
Safe insulation |
| IEC 61558-2-16 |
| IEC 61010-2-201 |
|
Permissible levels of harmonic current emissions |
|
Network fluctuation / undervoltage condition |
|