Product
|
Product type:
|
|
Product family:
|
|
AC mode
|
Input voltage range:
|
| The range is from 100 V AC to 240 V AC |
| Tolerance -15% ... +10 % |
| The range is from 115 V AC to 240 V AC |
| Tolerance ±10 % (UL) |
|
Frequency range (fN):
|
| 50 Hz to 60 Hz |
| Tolerance ±10 % |
|
Power backup time:
|
| > 23 ms (120 V AC) |
| > 24 ms (230 V AC) |
|
Current consumption:
|
| type. 5.3 A (100 V AC) |
| type. 4.4 A (120 V AC) |
| type. 2.3 A (230 V AC) |
| type. 2.15 A (240 V AC) |
|
Protection system:
|
| Protection against transient currents; Varistor |
|
DC mode
|
Input voltage range:
|
| The range is from 100 V DC to 240 V DC |
| Tolerance ±10 % |
| The range is from 160 V DC to 240 V DC |
| Tolerance ±10 % (UL) |
|
Current consumption:
|
| type. 5.2 A (100 V AC) |
| type. 2.1 A (240 V AC) |
|
Output data
|
Efficiency:
|
| type. 93.4 % (at 120 V AC) |
| type. 94.4 % (at 230 V AC) |
|
Reducing the rating parameters:
|
| < 100 V AC (1 % for each V) |
| > 60°C (2.5% for each K) |
|
output power:
|
|
Start-up time:
|
| ≤ 1 s (UOUT (10 % ... 90 %)) |
|
High reliability: MTBF
|
| > 790,000 hours at 25 °C |
| > 500,000 hours at 40 °C |
| > 240,000 hours at 60 °C |
|
Parallel connectivity:
|
|
Serial connectivity:
|
|
Syngalization
|
Signaling methods
|
| LED DC OK - signal status operation |
|
Function
|
| Visual indication of working condition. |
|
Assembly
|
Mounting method
|
| Mounting on a mounting rail |
|
Mounting position
|
| DIN rail horizontal NS 35, EN 60715 |
|
Dimensions
|
| Width: 88 mm |
| Height: 135 mm |
| Depth: 132 mm, 125 mm (Depth of device (DIN rail mounting)) |
|
Ambient conditions
|
Degree of protection
|
|
Ambient temperature
|
| from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations
|
EN 61010-1
|
| III (≤ 2000 m) |
| II (≤ 5000 m) |
|
EN 61010-2-201
|
| III (≤ 2000 m) |
| II (≤ 5000 m) |
|
Safety in the use of power supplies up to 1100 V (clearances insulation)
|
|
Electrical safety
|
|
Equipping electrical power equipment with auxiliary electronic devices
|
|
Safety requirements for measuring devices, control, regulation and laboratory
|
|
Very low voltage PELV
|
| IEC 61010-1 (SELV) |
| IEC 61010-2-201 (PELV) |
|
Safe insulation
|
| IEC 61558-2-16 |
| IEC 61010-2-201 |
|
Permissible levels of harmonic current emissions
|
|
Network fluctuation / undervoltage condition
|
|