TRIO3-PS/1AC/24DC/10/4C/IOL - Power supply | 1252696
- Primary circuit clocked power supplies, TRIO POWER, Push-in terminals, 4-channel electronic switch, IO-Link, Mounting on mounting rail, Input: 1-phase, Output: 24 V DC / 10 A, 24 V DC adjustable ... 28 V DC
Power supplies
Power supplies
Our power supplies are reliable and ideally suited for any application. In our diverse product portfolio, you will find DIN-rail power supplies that vary in design, power and features. This makes them an excellent choice for a wide range of industries, such as automotive, mechanical engineering, process industries, and for the shipbuilding industry.
Product |
Product type: |
|
Product family: |
|
AC mode |
Input voltage range: |
The range is from 100 V AC to 240 V AC |
Tolerance -15% ... +10 % |
The range is from 115 V AC to 240 V AC |
Tolerance ±10 % (UL) |
|
Frequency range (fN): |
50 Hz to 60 Hz |
Tolerance ±10 Hz |
|
Power backup time: |
type. 27 ms (120 V AC) |
type. 28 ms (230 V AC) |
|
Current consumption: |
type. 2.6 A (100 V AC) |
type. 2.2 A (120 V AC) |
type. 1.2 A (230 V AC) |
type. 1.1 A (240 V AC) |
|
Protection system : |
Protection against transient currents; Varistor |
|
DC mode |
Input voltage range: |
The range is from 100 V DC to 240 V DC |
Tolerance ±10 Hz |
The range is from 160 V DC to 240 V DC |
Tolerance ±10 % (UL) |
|
Current consumption: |
type. 2.7 A (100 V DC) |
type. 1.1 A (240 V DC) |
|
Output data |
Efficiency: |
type. 94.5 % (at 120 V AC) |
type. 95.5 % (at 230 V AC) |
|
Reducing the rating parameters: |
< 100 V AC (1 % for each V) |
> 60°C (2.5% for each K) |
|
output power: |
|
Start-up time: |
≤ 1 s (UOUT (10 % ... 90 %)) |
|
High reliability: MTBF |
> 1,300,000 hours at 25 °C |
> 860,000 hours at 40 °C |
> 400,000 hours at 60 °C |
|
Parallel connectivity: |
|
Serial connectivity: |
|
Syngalization |
Signaling methods |
LED DC OK - signal status operation |
|
Function |
Visual indication of working condition. |
|
Assembly |
Mounting method |
Mounting on a mounting rail |
|
Mounting position |
DIN rail horizontal NS 35, EN 60715 |
|
Dimensions |
Width: 68 mm |
Height: 135 mm |
Depth: 132 mm, 125 mm (Depth of device (DIN rail mounting)) |
|
Ambient conditions |
Degree of protection |
|
Ambient temperature |
from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations |
EN 61010-1 |
III (≤ 2000 m) |
II (≤ 5000 m) |
|
EN 61010-2-201 |
III (≤ 2000 m) |
II (≤ 5000 m) |
|
Safety in the use of power supplies up to 1100 V (clearances insulation) |
|
Electrical safety |
|
Equipping electrical power equipment with auxiliary electronic devices |
|
Safety requirements for measuring devices, control, regulation and laboratory |
|
Very low voltage PELV |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Safe insulation |
IEC 61558-2-16 |
IEC 61010-2-201 |
|
Permissible levels of harmonic current emissions |
|
Network fluctuation / undervoltage condition |
|
Benefits
- Power supply and contactors in one device thanks to built-in multi-channel protection – provides comprehensive protection for the device.
- Reduce installation costs by as much as 70% due to reduced wiring and installation requirements.
- Improved reliability with priority load management and intelligent automatic monitoring.
- Save space with compact width and ability to line up units.
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.