Product |
Product type: |
|
Product family: |
|
AC mode |
AC input voltage range: |
The range is from 220 V AC to 240 V AC |
Tolerance -15% ... +10 % |
|
AC frequency range: |
50 Hz to 60 Hz |
Tolerance ± 10% |
|
Power backup time: |
> 20 ms (190 V AC) |
> 20 ms (230 V AC) |
|
Current consumption: |
|
Rated current consumption: |
|
DC mode |
DC input voltage range: |
The range is from 220 V DC to 400 V DC |
Tolerance -15% ... +5 % |
|
Power backup time: |
> 20 ms (185 V DC) |
> 20 ms (400 V DC) |
|
Current consumption: |
type. 1.3 A (220 V DC) |
type. 0.7 A (400 V DC) |
|
Output data |
Efficiency: |
type. 92.5 % (230 V AC) |
type. 94 % (400 V AC) |
|
Reducing the rating parameters: |
60 °C to 70 °C (2.5 % for each K) |
|
Output power: |
|
Short circuit resistance and idle test: |
|
Start-up time: |
< 20 ms (UOut (10 % ... 90 %)) |
|
High reliability: MTBF |
> 2,220,000 hours at 25 °C |
> 1,280,000 hours at 40 °C |
> 560,000 hours at 60 °C |
> 2,220,000 hours at 25 °C |
> 1,280,000 hours at 40 °C |
> 560,000 hours at 60 °C |
|
Parallel connectivity: |
Yes, for redundancy and increased power |
|
Sygnalization |
Signaling methods |
Potential-free signaling contact |
|
Signaling designation |
|
Status indicator |
|
Assembly |
Mounting method |
Mounting on a mounting rail |
|
Mounting position |
DIN rail horizontal NS 35, EN 60715 |
|
Dimensional Drawing |
|
Dimensions |
Width: 42 mm |
Height: 130 mm |
Depth: 160 mm |
|
Ambient conditions |
Degree of protection |
|
Ambient temperature |
from -25 °C to 70 °C (Derating > 60 °C: 1.6 % for each K) |
|
Standard designation: Standards/Regulations |
Railroad applications |
EN 50121-3-2 |
EN 50121-4 |
EN 50124-1 |
EN 50125-3 |
IEC 62236-3-2 |
IEC 62236-4 |
IEC 62236-5 |
|
Normative limitation of higher harmonics of the network current |
|
Normative electrical safety |
EN 61010-1 |
IEC 62368-1 (SELV) |
|
Normative low protection voltage |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Normative certain separation |
IEC 61010-2-201 |
IEC 61558-2-16 |
|
Standard - Safety of use of power supplies up to 1100 V (insulation clearances) |
|