AC mode |
Input voltage range: |
The range is from 100 V AC to 240 V AC |
Tolerance -15% ... +10 % |
|
Frequency range (fN): |
50 Hz to 60 Hz |
Tolerance ±10 Hz |
|
Power backup time: |
> 20 ms (120 V AC) |
> 110 ms (230 V AC) |
|
Current consumption: |
type. 1.1 A (100 V AC) |
type. 1 A (120 V AC) |
type. 0.6 A (230 V AC) |
type. 0.6 A (240 V AC) |
|
Rated power consumption: |
|
Protection system: |
Protection against transient currents; Varistor |
|
DC mode |
Input voltage range: |
The range is from 99 V DC to 275 V DC |
Tolerance ±10 % |
The range is from 160 V DC to 240 V DC |
Tolerance ±10 % (UL) |
|
Current consumption: |
type. 0.7 A (110 V DC) |
type. 0.3 A (250 V DC) |
|
Output data |
Efficiency: |
type. 90.5 % (120 V AC) |
type. 91 % (230 V AC) |
|
Reducing the rating parameters: |
< 100 V AC (1 % for each V) |
> 60 °C (2.5% for each K) |
|
output power: |
|
Start-up time: |
≤ 10 s (UOUT (10 % ... 90 %)) |
|
High reliability: MTBF |
> 2,300,000 hours at 25 °C |
> 1,300,000 hours at 40 °C |
> 610,000 hours at 60 °C |
|
Parallel connectivity: |
yes, to increase power and redundancy |
|
Serial connectivity: |
yes, to increase the voltage (observe the SELV limit) |
|
Syngalization |
Signaling methods |
LED DC OK - signal status operation |
|
Function |
Visual indication of working condition. |
|
Assembly |
Mounting method |
Mounting on a mounting rail |
|
Mounting position |
DIN rail horizontal NS 35, EN 60715 |
|
Dimensions |
Width: 40 mm |
Height: 135 mm |
Depth: 132 mm, 125 mm (Depth of device – DIN rail mounting) |
|
Ambient conditions |
Degree of protection |
|
Ambient temperature |
from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations |
EN 60950-1 |
|
Normative equipment of electronic devices with electronic technical means
|
|
Normative limitation of higher harmonics of the network current |
|
Normative electrical safety |
|
Normative low protection voltage |
IEC 62368-1 (SELV) und EN 60204-1 (PELV) |
|
Normative certain separation |
|
Normative safety of transformers |
EN 61558-2-16 (surface and air insulation clearances only) |
|
Approval - semiconductor industry requirements for with respect to supply voltage drops.
|
|