Product |
Product type: |
|
Product family: |
|
AC mode |
Input voltage range: |
The range is from 100 V AC to 240 V AC |
Tolerance -15% ... +10 % |
|
Frequency range (fN): |
50 Hz to 60 Hz |
Tolerance ±10 Hz |
|
Power backup time: |
type. 35 ms (120 V AC) |
type. 35 ms (230 V AC) |
|
Current consumption: |
type. 1 A (100 V AC) |
type. 0.83 A (120 V AC) |
type. 0.46 A (230 V AC) |
type. 0.44 A (240 V AC) |
|
Rated power consumption : |
|
Protection system : |
Protection against transient currents; Varistor |
|
DC mode |
Input voltage range: |
The range is from 110 V DC to 250 V DC |
Tolerance -20 % ... +40 % |
|
Current consumption : |
0.91 A (110 V DC) |
0.4 A (250 V DC) |
|
Output data |
Efficiency: |
type. 92.8 % (120 V AC) |
type. 93.7 % (230 V AC) |
|
Short circuit resistance and idle test: |
|
output power: |
|
Start-up time: |
< 50 ms (UOut (10 % ... 90 %)) |
|
High reliability: MTBF |
> 1,272,000 hours at 25 °C |
> 690,000 hours at 40 °C |
> 271,000 hours at 60 °C |
|
Parallel connectivity: |
Yes, for redundancy and increased power |
|
Serial connectivity: |
|
Assembly |
Mounting method |
Mounting on a mounting rail |
|
Mounting position |
DIN rail horizontal NS 35, EN 60715 |
|
Dimensions |
|
Width: 45 mm |
Height: 106 mm |
Depth: 90 mm |
|
Ambient conditions |
Degree of protection |
|
Ambient temperature |
from -25 °C to 70 °C (> 60 °C derating: 2.5 % for each K) |
|
Standard designation: Standards/Regulations |
Normative limitation of higher harmonics of the network current |
|
Normative electrical safety |
|
Normative low protection voltage |
IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) |
|
Normative certain separation |
IEC 61558-2-16 |
IEC 61010-2-201 |
|
Standard - Safety requirements for equipment
measuring, control, regulation and laboratory equipment
|
|
Normative safety of transformers |
|
Charging the battery |
|
Approval - semiconductor industry requirements for
with respect to supply voltage drops.
|
SEMI F47-0706, EN 61000-4-11 |
|