Universal current measuring transducer, for DC, AC and distorted current measurement, input current 0 ... 600 A, output 4 ... 20 mA
Subscription products in your shopping cart
Choose one subscription frequency for all products in your cart or place separate orders for different renewal periods.
Set one delivery frequency for all subscription products in your cart every:
Subscription products in your shopping cart
In your shopping cart there are products with different subscription order renewal period. If you want to order products with different subscription period place a separate order.
AC Current Measuring Transducers and AC/DC Current Measuring Transducers
Here you will find the appropriate measuring transducer for measuring direct, alternating, and distorted currents. The range includes various options for a wide measuring range: from very small currents starting at 0 mA to 100 mA, up to higher currents of 600 A. To quickly add additional measuring points in existing installations, it is worth using versions with a removable Rogowski coil.
Product Features:
Product Type:
Current measuring transducer
Electrical Parameters
Power Supply Voltage Range:
from 20 V DC to 30 V DC
Maximum Current Consumption:
30 mA
Power Consumption:
1.65 W
Linearity Error:
<± 1% (of the full-scale range)
Maximum Power Loss under Nominal Conditions:
1 W
Step Response (10–90%):
< 150 ms
Max. Temperature Coefficient:
< 0.02 %/K (0 °C ... 60 °C)
< 0.04 %/K (-40 °C ... 65 °C)
Maximum Transmission Error:
<± 1% (limit value)
Rated Insulation Voltage
300 V AC (to ground)
Input Data
Input Current Range:
from 0 A AC/DC to 600 A AC/DC
Current Overload Capacity:
3.33 x IIN
Measured Frequency Range:
from 20 Hz to 6000 Hz
Output Data
Output Signal Current:
from 4 mA to 20 mA
Maximum Output Signal Current:
< 25 mA
Voltage Output Load/Power:
< 10 kΩ
Dimensions
Width:
90 mm
Height:
33.8 mm
Depth:
85 mm
Mounting Method:
DIN rail mounting
Ambient Conditions
Degree of Protection:
IP20
Ambient Temperature:
from -40 °C to 65 °C
Benefits
Option to equip with flexible Rogowski coils.
True RMS measurement in the range from 30 to 6000 Hz.
Measurement range adjustment using slide switches.
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.
If this description is not sufficient, please send us a question to this product. We will reply as soon as possible.
Data is processed in accordance with the privacy policy. By submitting data, you accept privacy policy provisions.
This page uses cookie files to provide its services in accordance to Cookies Usage Policy. You can determine conditions of storing or access to cookie files in your web browser.