  • MACX MCR voltage measuring transducers for DC voltages from 0... (+/-) 20 V DC to 0... .(+/-) 660 V DC, output signal (+/-) 10 V/ (+/-)20 mA

1 403,45 zł

net / 1szt.
Lowest price in 30 days before discount: / szt.
Regular price: / szt.
List price:
You can buy for pts.
of
Product available
Contact the shop staff, in order to estimate time of preparing this product for shipment.
Product available
Shipment
14 days for easy returns
This product is not available in a stationary store
Safe shopping
After purchase you will receive pts.

AC Current Transducers and AC/DC Current Measurement Transducers

Here you will find the appropriate measurement transducer for measuring direct, alternating, and distorted currents. The offer includes various options for a wide measurement range: from very small currents, starting from 0 mA to 100 mA, up to larger currents up to 600 A. To quickly add additional measurement points to existing installations, it is worth using variants with a removable Rogowski sensor.
AC Current Transducers and AC/DC Current Measurement Transducers

Product Features:

Product Type:

Voltage Measurement Transducer

Electrical Parameters

Power Supply Voltage Range:

from 19.2 V DC to 30 V DC

Maximum Current Consumption:

< 60 mA

Gain Compensation:

± 20 %

Zero Compensation:

± 20 %

Maximum Power Loss Under Nominal Conditions:

1.2 W

Step Response (10-90%):

< 16 ms

Maximum Temperature Coefficient:

< 0.015 %/K

Maximum Transfer Error:

< 1 % (end value of the measurement range)

Input Data - Measurements

Configurable/Programmable:

yes

Input Voltage Range:

from -550 V DC to 550 V DC

Output Resistance, Input Voltage:

5500 kΩ

Maximum Input Voltage:

± 660 V DC

Input Voltage Range:

from -370 V DC to 370 V DC

Output Resistance, Input Voltage:

3700 kΩ

Input Voltage Range:

from -250 V DC to 250 V DC

Output Resistance, Input Voltage:

2500 kΩ

Input Voltage Range:

from -170 V DC to 170 V DC

Output Resistance, Input Voltage:

1700 kΩ

Input Voltage Range:

from -120 V DC to 120 V DC

Output Resistance, Input Voltage:

1200 kΩ

Input Voltage Range:

from -80 V DC to 80 V DC

Output Resistance, Input Voltage:

800 kΩ

Input Voltage Range:

from -54 V DC to 54 V DC

Output Resistance, Input Voltage:

800 kΩ

Input Voltage Range:

from -36 V DC to 36 V DC

Output Resistance, Input Voltage:

800 kΩ

Input Voltage Range:

from -24 V DC to 24 V DC

Output Resistance, Input Voltage:

240 kΩ

Output Data: Voltage

Output Current Signal:

from -10 V to 10 V

Maximum Output Signal Current:

≤ 11 V

Voltage Output Load/Power:

> 10 kΩ

Output Data: Current

Output Current Signal:

from -20 mA to 20 mA

Maximum Output Signal Current:

≤ 22 mA

Current Output Load/Power:

< 500 Ω

Max. Capacitive Load:

< 1000 pF

Max. Inductive Load:

< 1 mH

Dimensions

Width:

22.5 mm

Height:

113 mm

Depth:

114mm

Mounting Method:

Rail Mounting

Environmental Conditions

Degree of Protection:

IP20

Ambient Temperature:

from -25 °C to 60 °C

Benefits

  • Adjustable voltage ranges
  • Bidirectional output signals
  • Measurement range learning mode