MACX MCR-SL-CAC- 5-I-UP - Current measuring transducer | 2810625
MACX MCR-SL-CAC- 5-I-UP - Current measuring transducer | 2810625
MACX MCR-SL-CAC- 5-I-UP - Current measuring transducer | 2810625
MACX MCR-SL-CAC- 5-I-UP - Current measuring transducer | 2810625
MACX MCR-SL-CAC- 5-I-UP - Current measuring transducer | 2810625
MACX MCR-SL-CAC- 5-I-UP - Current measuring transducer | 2810625

MACX MCR-SL-CAC- 5-I-UP - Current measuring transducer | 2810625

  • Current measuring transducer for 1 A and 5 A AC, output signal 0...20 mA or 4...20 mA, configurable via DIP switch, with LED status indication
930,10 zł
net / szt.
Lowest price in 30 days before discount: / szt.
Regular price: / szt.
14 days for easy returns
This product is not available in a stationary store
Safe shopping

AC Current Measuring Transducers and AC/DC Current Measuring Transducers

Here you will find the appropriate measuring transducer for measuring direct, alternating, and distorted currents. The offer includes various options for a wide measuring range: from very small currents starting at 0 mA to 100 mA, up to larger currents up to 600 A. To quickly add additional measuring points in existing installations, it is worth using variants with a removable Rogowski sensor.
AC and AC/DC Current Measuring Transducers

Product Features:

Product Type:

Current measuring transducer

Electrical Parameters

Supply Voltage Range:

from 19.2 V DC to 30 V DC

Maximum Current Consumption:

< 33 mA (24 V DC)

Power Consumption:

< 0.8 W (24 V DC)

Maximum Power Loss under Rated Conditions:

< 0.9 W (24 V DC)
< 3.4 W (230 V AC)

Step Response (10-90%):

≤ 300 ms
200 ms

Maximum Temperature Coefficient:

< 0.02 %/K

Typical Temperature Coefficient:

< 0.015 %/K

Maximum Transfer Error:

≤ 0.5 % (of rated range value under normal conditions)

Rated Insulation Voltage:

300 V AC (relative to ground)

Input Data

Input Current Range:

from 0 A AC to 1 A AC (configurable)
from 0 A AC to 5 A AC (configurable)

Input Voltage Signal:

≤ 300 V AC

Input Impedance:

< 50 mΩ

Current Overload Capacity:

2 x IN (continuous)

Current Load Capacity:

20 x IN (1 s)

Rated Frequency fN:

50 Hz

Measured Frequency Range:

from 45 Hz to 65 Hz

Output Data

Open-circuit Voltage:

15 V

Output Signal Current:

from 0 mA to 20 mA (configurable)
from 4 mA to 20 mA (configurable)

Maximum Output Signal Current:

25 mA

Load/Output Power Current:

< 500 Ω (20 mA)

Ripple:

< 10 mVSS (500 Ω / 20 mA)

Dimensions

Width:

22.5 mm

Height:

104 mm

Depth:

114.5 mm

Mounting Method:

DIN rail mounting

Ambient Conditions

Degree of Protection:

IP20

Ambient Temperature:

from -20 °C to 65 °C

Benefits

  • Optional equipment with flexible Rogowski coils.
  • True RMS measurement in the range of 30 to 6000 Hz.
  • Measuring range adjustment using sliding switches.
pixel
Wszystkie parametry znajdują się poniżej w karcie produktu
Do you need help? Do you have any questions?Ask a question and we'll respond promptly, publishing the most interesting questions and answers for others.
Ask a question
If this description is not sufficient, please send us a question to this product. We will reply as soon as possible. Data is processed in accordance with the privacy policy. By submitting data, you accept privacy policy provisions.