  • Current measuring transducer for 1 A and 5 A AC, output signal 0...20 mA or 4...20 mA, configurable via DIP switch, with LED status indication

930,10 zł

net / 1szt.
Lowest price in 30 days before discount: / szt.
Regular price: / szt.
Cena sugerowana:
You can buy for pts.
of
Product available
Contact the shop staff, in order to estimate time of preparing this product for shipment.
Product available
Shipment
14 days for easy returns
This product is not available in a stationary store
Safe shopping
After purchase you will receive pts.

AC Current Measuring Transducers and AC/DC Current Measuring Transducers

Here you will find the appropriate measuring transducer for measuring direct, alternating, and distorted currents. The offer includes various options for a wide measuring range: from very small currents starting at 0 mA to 100 mA, up to larger currents up to 600 A. To quickly add additional measuring points in existing installations, it is worth using variants with a removable Rogowski sensor.
AC and AC/DC Current Measuring Transducers

Product Features:

Product Type:

Current measuring transducer

Electrical Parameters

Supply Voltage Range:

from 19.2 V DC to 30 V DC

Maximum Current Consumption:

< 33 mA (24 V DC)

Power Consumption:

< 0.8 W (24 V DC)

Maximum Power Loss under Rated Conditions:

< 0.9 W (24 V DC)
< 3.4 W (230 V AC)

Step Response (10-90%):

≤ 300 ms
200 ms

Maximum Temperature Coefficient:

< 0.02 %/K

Typical Temperature Coefficient:

< 0.015 %/K

Maximum Transfer Error:

≤ 0.5 % (of rated range value under normal conditions)

Rated Insulation Voltage:

300 V AC (relative to ground)

Input Data

Input Current Range:

from 0 A AC to 1 A AC (configurable)
from 0 A AC to 5 A AC (configurable)

Input Voltage Signal:

≤ 300 V AC

Input Impedance:

< 50 mΩ

Current Overload Capacity:

2 x IN (continuous)

Current Load Capacity:

20 x IN (1 s)

Rated Frequency fN:

50 Hz

Measured Frequency Range:

from 45 Hz to 65 Hz

Output Data

Open-circuit Voltage:

15 V

Output Signal Current:

from 0 mA to 20 mA (configurable)
from 4 mA to 20 mA (configurable)

Maximum Output Signal Current:

25 mA

Load/Output Power Current:

< 500 Ω (20 mA)

Ripple:

< 10 mVSS (500 Ω / 20 mA)

Dimensions

Width:

22.5 mm

Height:

104 mm

Depth:

114.5 mm

Mounting Method:

DIN rail mounting

Ambient Conditions

Degree of Protection:

IP20

Ambient Temperature:

from -20 °C to 65 °C

Benefits

  • Optional equipment with flexible Rogowski coils.
  • True RMS measurement in the range of 30 to 6000 Hz.
  • Measuring range adjustment using sliding switches.