Product |
Product type: | |
Product family: | |
AC mode |
Input voltage range: | The range is from 100V AC to 240V AC | Tolerance -15% ... +10 % | |
Frequency range : | 50 Hz to 60 Hz | Tolerance ± 10% | |
Power backup time: | > 25 ms (120 V AC) | > 25 ms (230 V AC) | |
Current consumption: | type. 1.34 A (100 V AC) | type. 1.1 A (120 V AC) | type. 0.59 A (230 V AC) | type. 0.57 A (240 V AC) | |
Protection system: | Transient overvoltage protection; Varistor | |
Input fuse: | 3.15 A internal (equipment protection),delayed | |
Output data | Efficiency: | type. 93 % (120 V AC) | type. 94 % (230 V AC) | |
Rated output voltage: | |
Rated output current (IN): | |
Short circuit resistance and idle test: | |
Reducing the rating parameters: | < 100 V AC (1 % for each V) | |
output power: | |
Start-up time: | < 1 s (UOut = 10 % ... 90 %) | |
High MTBF reliability: | > 1,442,000 hours at 25 °C | > 813,000 hours at 40 °C | > 428,000 hours at 55 °C | |
Parallel connection possible: | yes, to increase power and redundancy with diode | |
Serial connectivity: | yes, to increase the voltage | |
Syngalization | Signaling methods | LED DC OK - operation signal status (UN = 24 V DC, IOut = IN) | |
Function | Visual indication of working condition. | |
Assembly | Mounting method | Mounting on a mounting rail | |
Mounting position | DIN rail horizontal NS 35, EN 60715 | |
Dimensions | Width: 35 mm | Height: 130 mm | Depth: 129 mm, 125 mm (Depth of device (DIN rail mounting)) | |
Ambient conditions | Degree of protection | |
Ambient temperature | from -25 °C to 70 °C (> 55 °C reduction: 2.5 % for each K) | |
Standard designation: Standards/Regulations | Surge category | EN 61010-1 | II (≤ 4000 m) | | EN 62477-1 | III (≤ 3000 m) | |
Safety of use of power supplies up to 1100 V (insulation gaps) | |
Electrical safety | |
Normative electrical safety | |
Equipping power equipment with auxiliary electronic devices | |
Safety requirements for measuring, control, regulation and laboratory equipment | |
Very low voltage PELV | IEC 61010-1 (SELV) | IEC 61010-2-201 (PELV) | |
Safe insulation | IEC 61558-2-16 | IEC 61010-2-201 | |
Permissible levels of harmonic current emissions | |
The requirements of the semiconductor industry in with regard to voltage drops in the supply | SEMI F47 - 0706 (180 V AC) | |