Product |
---|
Product type: | |
Product family: | |
AC mode |
---|
AC input voltage range: | The range is from 220 V AC to 240 V AC | Tolerance -15% ... +10 % | |
---|
AC frequency range: | 50 Hz to 60 Hz | Tolerance ± 10% | |
Power backup time: | > 20 ms (190 V AC) | > 20 ms (230 V AC) | |
Current consumption: | |
Rated current consumption: | |
DC mode |
DC input voltage range: | The range is from 220 V DC to 400 V DC | Tolerance -15% ... +5 % | |
Power backup time: | > 20 ms (185 V DC) | > 20 ms (400 V DC) | |
Current consumption: | type. 1.3 A (220 V DC) | type. 0.7 A (400 V DC) | |
Output data | Efficiency: | type. 92.5 % (230 V AC) | type. 94 % (400 V AC) | |
Reducing the rating parameters: | 60 °C to 70 °C (2.5 % for each K) | |
output power: | |
Short circuit resistance and idle test: | |
Start-up time: | < 20 ms (UOut (10 % ... 90 %)) | |
High reliability: MTBF | > 2,220,000 hours at 25 °C | > 1,280,000 hours at 40 °C | > 560,000 hours at 60 °C | > 2,220,000 hours at 25 °C | > 1,280,000 hours at 40 °C | > 560,000 hours at 60 °C | |
Parallel connectivity: | Yes, for redundancy and increased power | |
Syngalization | Signaling methods | Potential-free signaling contact | |
Signaling designation | |
Status indicator | |
Assembly | Mounting method | Mounting on a mounting rail | |
Mounting position | DIN rail horizontal NS 35, EN 60715 | |
Dimensional Drawing | |
Dimensions | Width: 42 mm | Height: 130 mm | Depth: 160 mm | |
Ambient conditions | Degree of protection | |
Ambient temperature | from -25 °C to 70 °C (Derating > 60 °C: 1.6 % for each K) | |
Standard designation: Standards/Regulations | Railroad applications | EN 50121-3-2 | EN 50121-4 | EN 50124-1 | EN 50125-3 | IEC 62236-3-2 | IEC 62236-4 | IEC 62236-5 | |
Normative limitation of higher harmonics of the network current | |
Normative electrical safety | EN 61010-1 | IEC 62368-1 (SELV) | |
Normative low protection voltage | IEC 61010-1 (SELV) | IEC 61010-2-201 (PELV) | |
Normative certain separation | IEC 61010-2-201 | IEC 61558-2-16 | |
Standard - Safety of use of power supplies up to 1100 V (insulation clearances) | |